VIoT 4-20mA Node

Getting Started

Installation and input scaling for the connected transmitter.

The 4-20mA Node is described in Vandyam's catalogue as a "Plug and Play Device," which reflects a simpler configuration story than the RS-485 Node: because it reads a single current-loop input rather than managing multiple Modbus slaves with custom register maps, there is far less to configure in the first place. The main setup decision is the input scaling — mapping the 4mA and 20mA endpoints of the loop to the real-world minimum and maximum values of whatever the connected transmitter measures (for example, 4mA = 0 bar and 20mA = 10 bar for a pressure transmitter).

Data path

Sensor → VIoT Node → VIoT Gateway → Cloud Dashboard → Alerts. Once wired and powered, the node joins the nearest Vandyam VIoT Gateway over LoRaWAN and begins reporting its current-loop reading.

  1. 1Mount the node near the 4-20mA transmitter and wire the current loop and 12V DC power
  2. 2Power on the node — it automatically attempts to join the nearest Vandyam VIoT Gateway over LoRaWAN
  3. 3Confirm on the Cloud Dashboard that the node has joined the network and is visible
  4. 4Set or confirm the 4-20mA scaling range for the connected instrument
  5. 5Verify live readings are arriving on the dashboard before leaving site